Notifications
You must be signed in to change notification settings - Fork 1
/
Copy pathheatpump.yaml
2967 lines (2899 loc) · 94.9 KB
/
heatpump.yaml
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
231
232
233
234
235
236
237
238
239
240
241
242
243
244
245
246
247
248
249
250
251
252
253
254
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
285
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
388
389
390
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
412
413
414
415
416
417
418
419
420
421
422
423
424
425
426
427
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
447
448
449
450
451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480
481
482
483
484
485
486
487
488
489
490
491
492
493
494
495
496
497
498
499
500
501
502
503
504
505
506
507
508
509
510
511
512
513
514
515
516
517
518
519
520
521
522
523
524
525
526
527
528
529
530
531
532
533
534
535
536
537
538
539
540
541
542
543
544
545
546
547
548
549
550
551
552
553
554
555
556
557
558
559
560
561
562
563
564
565
566
567
568
569
570
571
572
573
574
575
576
577
578
579
580
581
582
583
584
585
586
587
588
589
590
591
592
593
594
595
596
597
598
599
600
601
602
603
604
605
606
607
608
609
610
611
612
613
614
615
616
617
618
619
620
621
622
623
624
625
626
627
628
629
630
631
632
633
634
635
636
637
638
639
640
641
642
643
644
645
646
647
648
649
650
651
652
653
654
655
656
657
658
659
660
661
662
663
664
665
666
667
668
669
670
671
672
673
674
675
676
677
678
679
680
681
682
683
684
685
686
687
688
689
690
691
692
693
694
695
696
697
698
699
700
701
702
703
704
705
706
707
708
709
710
711
712
713
714
715
716
717
718
719
720
721
722
723
724
725
726
727
728
729
730
731
732
733
734
735
736
737
738
739
740
741
742
743
744
745
746
747
748
749
750
751
752
753
754
755
756
757
758
759
760
761
762
763
764
765
766
767
768
769
770
771
772
773
774
775
776
777
778
779
780
781
782
783
784
785
786
787
788
789
790
791
792
793
794
795
796
797
798
799
800
801
802
803
804
805
806
807
808
809
810
811
812
813
814
815
816
817
818
819
820
821
822
823
824
825
826
827
828
829
830
831
832
833
834
835
836
837
838
839
840
841
842
843
844
845
846
847
848
849
850
851
852
853
854
855
856
857
858
859
860
861
862
863
864
865
866
867
868
869
870
871
872
873
874
875
876
877
878
879
880
881
882
883
884
885
886
887
888
889
890
891
892
893
894
895
896
897
898
899
900
901
902
903
904
905
906
907
908
909
910
911
912
913
914
915
916
917
918
919
920
921
922
923
924
925
926
927
928
929
930
931
932
933
934
935
936
937
938
939
940
941
942
943
944
945
946
947
948
949
950
951
952
953
954
955
956
957
958
959
960
961
962
963
964
965
966
967
968
969
970
971
972
973
974
975
976
977
978
979
980
981
982
983
984
985
986
987
988
989
990
991
992
993
994
995
996
997
998
999
1000
substitutions:
devicename: heatpump
description: Heatpump Controller
entity_prefix: Heatpump
globals:
- id: unmasked_value_water_temperature_t1s
type: int
restore_value: no
initial_value: '0'
- id: unmasked_curve_selection
type: int
restore_value: no
initial_value: '0'
esphome:
name: "${devicename}"
comment: "${description}"
friendly_name: "${description}"
esp32:
board: esp32dev
framework:
type: arduino
# Enable logging
logger:
level: INFO
baud_rate: 0
# Enable Home Assistant API
api:
web_server:
port: 80
ota:
wifi:
power_save_mode: none
ssid: !secret wifi_ssid
password: !secret wifi_password
# Enable fallback hotspot (captive portal) in case wifi connection fails
ap:
ssid: "${devicename}-setup"
password: "heatpump"
captive_portal:
uart:
id: mod_bus
tx_pin: 17
rx_pin: 16
baud_rate: 9600
stop_bits: 1
modbus:
flow_control_pin: 5
id: heatpump_modbus
modbus_controller:
- id: "${devicename}"
## the Modbus device addr
address: 0x1
modbus_id: heatpump_modbus
setup_priority: -10
update_interval: 10s
sensor:
- platform: uptime
name: "${entity_prefix} Uptime"
# Register: 1
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Operational Mode"
id: "${devicename}_operational_mode"
register_type: holding
address: 0x1
value_type: U_WORD
# Register: 2 -> Is present in this config as a 'number'
# Register: 3
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Air Temperature Ts"
id: "${devicename}_air_temperature_ts"
register_type: holding
address: 0x3
value_type: U_WORD
unit_of_measurement: "°C"
filters:
- multiply: 0.5
# Register: 4
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} DHW Tank Temperature T5s"
id: "${devicename}_dhw_tank_temperature_t5s"
register_type: holding
address: 0x4
value_type: S_WORD
unit_of_measurement: "°C"
# Register: 6 -> Is present in this config as a 'number'
# Register: 7
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Forced Water Tank Heating"
id: "${devicename}_forced_water_tank_heating"
register_type: holding
address: 0x7
value_type: U_WORD
# Register: 8
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Forced Tank Backup Heater"
id: "${devicename}_forced_tbh"
register_type: holding
address: 0x8
value_type: U_WORD
# Register: 9
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Forced Hydraulic Module Rear Electric Heater 1"
id: "${devicename}_forced_hydraulic_module_rear_electric_heater_1"
register_type: holding
address: 0x9
value_type: U_WORD
# Register: 10
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} t_SG_MAX"
id: "${devicename}_t_sg_max"
register_type: holding
address: 0xa
value_type: U_WORD
unit_of_measurement: hr
# Register: 100
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Compressor Operating Frequency"
id: "${devicename}_compressor_operating_frequency"
register_type: holding
address: 0x64
value_type: U_WORD
unit_of_measurement: Hz
# Register: 101
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Operating Mode"
id: "${devicename}_operating_mode"
register_type: holding
address: 0x65
value_type: U_WORD
# Register: 102
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Fan Speed"
id: "${devicename}_fan_speed"
register_type: holding
address: 0x66
unit_of_measurement: "r/min"
value_type: U_WORD
icon: mdi:fan
# Register: 103
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} PMV Openness"
id: "${devicename}_pmv_openness"
register_type: holding
address: 0x67
value_type: U_WORD
unit_of_measurement: "Pa"
# Register: 104
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Water Inlet Temperature"
id: "${devicename}_water_inlet_temperature"
register_type: holding
address: 0x68
value_type: S_WORD
unit_of_measurement: "°C"
# Register: 105
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Water Outlet Temperature"
id: "${devicename}_water_outlet_temperature"
register_type: holding
address: 0x69
value_type: S_WORD
unit_of_measurement: "°C"
# Register: 106
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Condensor Temperature T3"
id: "${devicename}_condensor_temperature_t3"
register_type: holding
address: 0x6a
value_type: S_WORD
unit_of_measurement: "°C"
# Register: 107
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Outdoor Ambient Temperature"
id: "${devicename}_outdoor_ambient_temperature"
register_type: holding
address: 0x6B
unit_of_measurement: "°C"
value_type: S_WORD
# Register: 108
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Discharge Temperature"
id: "${devicename}_discharge_temperature"
register_type: holding
address: 0x6c
value_type: S_WORD
unit_of_measurement: "°C"
# Register: 109
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Return Air Temperature"
id: "${devicename}_return_air_temperature"
register_type: holding
address: 0x6d
value_type: S_WORD
unit_of_measurement: "°C"
# Register: 110
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Total Water Outlet Temperature T1"
id: "${devicename}_total_water_outlet_temperature_t1"
register_type: holding
address: 0x6e
value_type: S_WORD
unit_of_measurement: "°C"
# Register: 111
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} System Total Water Outlet Temperature T1B"
id: "${devicename}_system_total_water_outlet_temperature_t1b"
register_type: holding
address: 0x6f
value_type: S_WORD
unit_of_measurement: "°C"
# Register: 112
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Refrigerant Liquid Side Temperature T2"
id: "${devicename}_refrigerant_liquid_side_temperature_t2"
register_type: holding
address: 0x70
value_type: S_WORD
unit_of_measurement: "°C"
# Register: 113
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Refrigerant Gas Side Temperature T2B"
id: "${devicename}_refrigerant_gas_side_temperature_t2b"
register_type: holding
address: 0x71
value_type: S_WORD
unit_of_measurement: "°C"
# Register: 114
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Room Temperature Ta"
id: "${devicename}_room_temperature_ta"
register_type: holding
address: 0x72
value_type: S_WORD
unit_of_measurement: "°C"
# Register: 115
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Water Tank Temperature T5"
id: "${devicename}_water_tank_temperature_t5"
register_type: holding
address: 0x73
unit_of_measurement: "°C"
value_type: S_WORD
icon: mdi:thermometer-water
# Register: 116
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Outdoor Unit High Pressure"
id: "${devicename}_outdoor_unit_high_pressure"
register_type: holding
address: 0x74
value_type: U_WORD
unit_of_measurement: kPA
# Register: 117
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Outdoor Unit Low Pressure"
id: "${devicename}_outdoor_unit_low_pressure"
register_type: holding
address: 0x75
value_type: U_WORD
unit_of_measurement: kPA
# Register: 118
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Outdoor Unit Current"
id: "${devicename}_outdoor_unit_current"
register_type: holding
address: 0x76
value_type: U_WORD
unit_of_measurement: A
# Register: 119
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Outdoor Unit Voltage"
id: "${devicename}_outdoor_unit_voltage"
register_type: holding
address: 0x77
value_type: U_WORD
unit_of_measurement: V
# Register: 120
# Midea: Tbt1
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Hydraulic Module Current 1"
id: "${devicename}_hydraulic_module_current_1"
register_type: holding
address: 0x78
value_type: U_WORD
# Register: 121
# Midea: Tbt2
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Hydraulic Module Current 2"
id: "${devicename}_hydraulic_module_current_2"
register_type: holding
address: 0x79
value_type: U_WORD
# Register: 122
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Compressor Operation Time"
id: "${devicename}_compressor_operation_time"
register_type: holding
address: 0x7a
value_type: U_WORD
unit_of_measurement: hr
# Register: 123
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Unit Capacity"
id: "${devicename}_unit_capacity"
register_type: holding
address: 0x7b
value_type: U_WORD
# Register: 124
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Current Fault"
id: "${devicename}_current_fault"
register_type: holding
entity_category: diagnostic
address: 0x7c
value_type: U_WORD
# Register: 125
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Fault 1"
id: "${devicename}_fault_1"
register_type: holding
entity_category: diagnostic
address: 0x7d
value_type: U_WORD
# Register: 126
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Fault 2"
id: "${devicename}_fault_2"
register_type: holding
entity_category: diagnostic
address: 0x7e
value_type: U_WORD
# Register: 127
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Fault 3"
id: "${devicename}_fault_3"
register_type: holding
entity_category: diagnostic
address: 0x7f
value_type: U_WORD
# Register: 130
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Software Version"
id: "${devicename}_software_version"
register_type: holding
address: 0x82
value_type: U_WORD
# Register: 131
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Wired Controller Version Number"
id: "${devicename}_wired_controller_version_number"
register_type: holding
address: 0x83
value_type: U_WORD
# Register: 132
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Compressor Target Frequency"
id: "${devicename}_compressor_target_frequency"
register_type: holding
address: 0x84
value_type: U_WORD
unit_of_measurement: Hz
# Register: 133
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} DC Bus Current"
id: "${devicename}_dc_bus_current"
register_type: holding
address: 0x85
value_type: U_WORD
unit_of_measurement: A
# Register: 134
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} DC Bus Voltage"
id: "${devicename}_dc_bus_voltage"
register_type: holding
address: 0x86
value_type: U_WORD
unit_of_measurement: V
filters:
- multiply: 10
# Register: 135
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} TF module temperature"
id: "${devicename}_tf_module_temperature"
register_type: holding
address: 0x87
unit_of_measurement: "°C"
value_type: S_WORD
# Register: 136
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Climate Curve T1S Calculated Value 1"
id: "${devicename}_climate_curve_t1s_calculated_value_1"
register_type: holding
address: 0x88
value_type: S_WORD
unit_of_measurement: "°C"
# Register: 137
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Climate Curve T1S Calculated Value 2"
id: "${devicename}_climate_curve_t1s_calculated_value_2"
register_type: holding
address: 0x89
value_type: S_WORD
unit_of_measurement: "°C"
# Register: 138
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Water Flow"
id: "${devicename}_water_flow"
register_type: holding
address: 0x8a
value_type: U_WORD
unit_of_measurement: m3/H
accuracy_decimals: 2
filters:
- lambda: return x * 0.01;
# Register: 139
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Limit Scheme Of Outdoor Unit Current"
id: "${devicename}_limit_scheme_of_outdoor_unit_current"
register_type: holding
address: 0x8b
value_type: U_WORD
# Register: 140
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Ability Of Hydraulic Module"
id: "${devicename}_ability_of_hydraulic_module"
register_type: holding
address: 0x8c
value_type: U_WORD
unit_of_measurement: kW
accuracy_decimals: 2
filters:
- lambda: return x * 0.01;
# Register: 141
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Tsolar"
id: "${devicename}_tsolar"
register_type: holding
address: 0x8d
value_type: U_WORD
# Register: 143 and 144
# U_DWORD combines this register with the next one
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Electricity Consumption"
id: "${devicename}_electricity_consumption"
register_type: holding
unit_of_measurement: "kWh"
state_class: total_increasing
address: 0x8f
value_type: U_DWORD
# Register: 145 and 146
# U_DWORD combines this register with the next one
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Output"
id: "${devicename}_power_output"
register_type: holding
unit_of_measurement: "kWh"
state_class: total_increasing
address: 0x91
value_type: U_DWORD
# Register: 200 (High byte)
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Home Appliance Type"
id: "${devicename}_home_appliance_type"
register_type: holding
address: 0xc8
value_type: U_WORD
bitmask: 0x00FF
# Register: 200 (Low byte, first 4 bits)
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Home Appliance Sub Type"
id: "${devicename}_home_appliance_sub_type"
register_type: holding
address: 0xc8
value_type: U_WORD
bitmask: 0xF000
# Register: 200 (Low byte, second 4 bits)
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Home Appliance Product Code"
id: "${devicename}_home_appliance_product_code"
register_type: holding
address: 0xc8
value_type: U_WORD
bitmask: 0x0F00
# Register: 201 (Low), default: 25, TODO: verify default
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Temperature Upper Limit Of T1S Cooling Zone 1"
id: "${devicename}_temperature_upper_limit_of_t1s_cooling_zone_1"
register_type: holding
address: 0xc9
value_type: S_WORD
unit_of_measurement: "°C"
bitmask: 0x00FF
# Register: 201 (High), default: 25, TODO: verify default
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Temperature Upper Limit Of T1S Cooling Zone 2"
id: "${devicename}_temperature_upper_limit_of_t1s_cooling_zone_2"
register_type: holding
address: 0xc9
value_type: S_WORD
unit_of_measurement: "°C"
bitmask: 0xFF00
# Register: 202 (Low), default: 5, TODO: verify default
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Temperature Lower Limit Of T1S Cooling Zone 1"
id: "${devicename}_temperature_lower_limit_of_t1s_cooling_zone_1"
register_type: holding
address: 0xca
value_type: S_WORD
unit_of_measurement: "°C"
bitmask: 0x00FF
# Register: 202 (High), default: 5, TODO: verify default
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Temperature Lower Limit Of T1S Cooling Zone 2"
id: "${devicename}_temperature_lower_limit_of_t1s_cooling_zone_2"
register_type: holding
address: 0xca
value_type: S_WORD
unit_of_measurement: "°C"
bitmask: 0xFF00
# Register: 203 (Low), default: 55, TODO: verify default
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Temperature Upper Limit Of T1S Heating Zone 1"
id: "${devicename}_temperature_upper_limit_of_t1s_heating_zone_1"
register_type: holding
address: 0xcb
value_type: S_WORD
unit_of_measurement: "°C"
bitmask: 0x00FF
# Register: 203 (High), default: 55, TODO: verify default
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Temperature Upper Limit Of T1S Heating Zone 2"
id: "${devicename}_temperature_upper_limit_of_t1s_heating_zone_2"
register_type: holding
address: 0xcb
value_type: S_WORD
unit_of_measurement: "°C"
bitmask: 0xFF00
# Register: 204 (Low), default: 25, TODO: verify default
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Temperature Lower Limit Of T1S Heating Zone 1"
id: "${devicename}_temperature_lower_limit_of_t1s_heating_zone_1"
register_type: holding
address: 0xcc
value_type: S_WORD
unit_of_measurement: "°C"
bitmask: 0x00FF
# Register: 204 (High), default: 25, TODO: verify default
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Temperature Lower Limit Of T1S Heating Zone 2"
id: "${devicename}_temperature_lower_limit_of_t1s_heating_zone_2"
register_type: holding
address: 0xcc
value_type: S_WORD
unit_of_measurement: "°C"
bitmask: 0xFF00
# Register: 205 -> Is present in this config as a 'number'
# Register: 206 -> Is present in this config as a 'number'
# Register: 207 -> Is present in this config as a 'number'
# Register: 208 -> Is present in this config as a 'number'
# Register: 209 -> Is present in this config as a 'number'
# Register: 212 -> Is present in this config as a 'number'
# Register: 213 -> Is present in this config as a 'number'
# Register: 214 -> Is present in this config as a 'number'
# Register: 215 -> Is present in this config as a 'number'
# Register: 216 -> Is present in this config as a 'number'
# Register: 217 -> Is present in this config as a 'number'
# Register: 218 -> Is present in this config as a 'number'
# Register: 219 -> Is present in this config as a 'number'
# Register: 220 -> Is present in this config as a 'number'
# Register: 221 -> Is present in this config as a 'number'
# Register: 222 -> Is present in this config as a 'number'
# Register: 223 -> Is present in this config as a 'number'
# Register: 224 -> Is present in this config as a 'number'
# Register: 225 -> Is present in this config as a 'number'
# Register: 226 -> Is present in this config as a 'number'
# Register: 227 -> Is present in this config as a 'number'
# Register: 228 -> Is present in this config as a 'number'
# Register: 229 -> Is present in this config as a 'number'
# Register: 230 -> Is present in this config as a 'number'
# Register: 231 -> Is present in this config as a 'number'
# Register: 232 -> Is present in this config as a 'number'
# Register: 233 -> Is present in this config as a 'number'
# Register: 234 -> Is present in this config as a 'number'
# Register: 235 -> Is present in this config as a 'number'
# Register: 237 -> Is present in this config as a 'number'
# Register: 238 -> Is present in this config as a 'number'
# Register: 240 -> Is present in this config as a 'number'
# Register: 241 -> Is present in this config as a 'number'
# Register: 242 -> Is present in this config as a 'number'
# Register: 243 -> Is present in this config as a 'number'
# Register: 244 -> Is present in this config as a 'number'
# Register: 245 -> Is present in this config as a 'number'
# Register: 246 -> Is present in this config as a 'number'
# Register: 247 -> Is present in this config as a 'number'
# Register: 248 -> Is present in this config as a 'number'
# Register: 249 -> Is present in this config as a 'number'
# Register: 250 -> Is present in this config as a 'number'
# Register: 251 -> Is present in this config as a 'number'
# Register: 252 -> Is present in this config as a 'number'
# Register: 253
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Comfort Parameter Reserved 3"
id: "${devicename}_comfort_parameter_3"
register_type: holding
address: 0xfd
value_type: U_WORD
# Register: 254
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Comfort Parameter Reserved 4"
id: "${devicename}_comfort_parameter_4"
register_type: holding
address: 0xfe
value_type: U_WORD
# Register: 255 -> Is present in this config as a 'number'
# Register: 256 -> Is present in this config as a 'number'
# Register: 257 -> Is present in this config as a 'number'
# Register: 258 -> Is present in this config as a 'number'
# Register: 259 -> Is present in this config as a 'number'
# Register: 260 -> Is present in this config as a 'number'
# Register: 261 -> Is present in this config as a 'number'
# Register: 262 -> Is present in this config as a 'number'
# Register: 263 -> Is present in this config as a 'number'
# Register: 264 -> Is present in this config as a 'number'
# Register: 265 -> Is present in this config as a 'number'
# Register: 266 -> Is present in this config as a 'number'
# Register: 267 -> Is present in this config as a 'number'
# Register: 268 -> Is present in this config as a 'number'
# Register: 269, default: 0
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Input Limitation Type"
id: "${devicename}_power_input_limitation_type"
register_type: holding
address: 0x10d
value_type: U_WORD
# Register: 270 (Low), default: 0.5, TODO: verify default
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} t_T4 FRESH_H"
id: "${devicename}_t_t4_fresh_h"
register_type: holding
address: 0x10e
value_type: U_WORD
unit_of_measurement: hr
accuracy_decimals: 1
bitmask: 0x00FF
filters:
- multiply: 0.5
# Register: 270 (High), default: 0.5, TODO: verify default
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} t_T4 FRESH_C"
id: "${devicename}_t_t4_fresh_c"
register_type: holding
address: 0x10e
value_type: U_WORD
unit_of_measurement: hr
accuracy_decimals: 1
bitmask: 0xFF00
filters:
- multiply: 0.5
# Register: 271, default: 2, TODO: verify default
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Built-in Circulating Pump Delay"
id: "${devicename}_t_pumpi_delay"
register_type: holding
address: 0x10f
value_type: U_WORD
unit_of_measurement: hr
filters:
- multiply: 0.5
# Register: 272 (Low, first 4 bits), default: 0, TODO: verify default
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Zone 1 End Heating Mode Emission Type"
id: "${devicename}_zone_1_end_heating_mod_emission_type"
register_type: holding
address: 0x110
value_type: U_WORD
bitmask: 0xF000
# Register: 272 (Low, second 4 bits), default: 0, TODO: verify default
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Zone 2 End Heating Mode Emission Type"
id: "${devicename}_zone_2_end_heating_mod_emission_type"
register_type: holding
address: 0x110
value_type: U_WORD
bitmask: 0x0F00
# Register: 272 (High, first 4 bits), default: 2, TODO: verify default
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Zone 1 End Cooling Mode Emission Type"
id: "${devicename}_zone_1_end_cooling_mod_emission_type"
register_type: holding
address: 0x110
value_type: U_WORD
bitmask: 0x00F0
# Register: 272 (High, second 4 bits), default: 2, TODO: verify default
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Zone 2 End Cooling Mode Emission Type"
id: "${devicename}_zone_2_end_cooling_mod_emission_type"
register_type: holding
address: 0x110
value_type: U_WORD
bitmask: 0x000F
binary_sensor:
# Register: 0
# Bit: 0
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Floor Heating Zone 1"
id: "${devicename}_power_floor_heating_zone_1"
register_type: holding
address: 0x0
bitmask: 0x1
# Bit: 1
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Air Conditioner Zone 1"
id: "${devicename}_power_air_conditioner_zone_1"
register_type: holding
address: 0x0
bitmask: 0x2
# Bit: 2 -> Is present in this config as a 'switch'
# Bit: 3
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Air Conditioner Zone 2"
id: "${devicename}_power_air_conditioner_zone_2"
register_type: holding
address: 0x0
bitmask: 0x8
# Bit: 4
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Reserved BIT 4"
id: "${devicename}_power_reserved_bit_4"
register_type: holding
address: 0x0
bitmask: 0x10
# Bit: 5
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Reserved BIT 5"
id: "${devicename}_power_reserved_bit_5"
register_type: holding
address: 0x0
bitmask: 0x20
# Bit: 6
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Reserved BIT 6"
id: "${devicename}_power_reserved_bit_6"
register_type: holding
address: 0x0
bitmask: 0x40
# Bit: 7
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Reserved BIT 7"
id: "${devicename}_power_reserved_bit_7"
register_type: holding
address: 0x0
bitmask: 0x80
# Bit: 8
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Reserved BIT 8"
id: "${devicename}_power_reserved_bit_8"
register_type: holding
address: 0x0
bitmask: 0x100
# Bit: 9
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Reserved BIT 9"
id: "${devicename}_power_reserved_bit_9"
register_type: holding
address: 0x0
bitmask: 0x200
# Bit: 10
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Reserved BIT 10"
id: "${devicename}_power_reserved_bit_10"
register_type: holding
address: 0x0
bitmask: 0x400
# Bit: 11
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Reserved BIT 11"
id: "${devicename}_power_reserved_bit_11"
register_type: holding
address: 0x0
bitmask: 0x800
# Bit: 12
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Reserved BIT 12"
id: "${devicename}_power_reserved_bit_12"
register_type: holding
address: 0x0
bitmask: 0x1000
# Bit: 13
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Reserved BIT 13"
id: "${devicename}_power_reserved_bit_13"
register_type: holding
address: 0x0
bitmask: 0x2000
# Bit: 14
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Reserved BIT 14"
id: "${devicename}_power_reserved_bit_14"
register_type: holding
address: 0x0
bitmask: 0x4000
# Bit: 15
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Power Reserved BIT 15"
id: "${devicename}_power_reserved_bit_15"
register_type: holding
address: 0x0
bitmask: 0x8000
# Register: 5
# Bit: 0
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Function Setting Reserved BIT 0"
id: "${devicename}_function_setting_reserved_bit_0"
register_type: holding
address: 0x5
bitmask: 0x1
# Bit: 1
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Function Setting Reserved BIT 1"
id: "${devicename}_function_setting_reserved_bit_1"
register_type: holding
address: 0x5
bitmask: 0x2
# Bit: 2
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Function Setting Reserved BIT 2"
id: "${devicename}_function_setting_reserved_bit_2"
register_type: holding
address: 0x5
bitmask: 0x4
# Bit: 3
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Function Setting Reserved BIT 3"
id: "${devicename}_function_setting_reserved_bit_3"
register_type: holding
address: 0x5
bitmask: 0x8
# Bit: 4
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Function Setting Disinfect"
id: "${devicename}_function_setting_disinfect"
register_type: holding
address: 0x5
bitmask: 0x10
# Bit: 5
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Function Setting Holiday Away"
id: "${devicename}_function_setting_holiday_away"
register_type: holding
address: 0x5
bitmask: 0x20
# Bit: 6
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Function Setting Silent Mode"
id: "${devicename}_function_setting_silent_mode"
register_type: holding
address: 0x5
bitmask: 0x40
# Bit: 7
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Function Setting Silent Mode Level"
id: "${devicename}_function_setting_silent_mode_level"
register_type: holding
address: 0x5
bitmask: 0x80
# Bit: 8
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Function Setting Holiday Home"
id: "${devicename}_function_setting_holiday_home"
register_type: holding
address: 0x5
bitmask: 0x100
# Bit: 9
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Function Setting Reserved BIT 9"
id: "${devicename}_function_setting_reserved_bit_9"
register_type: holding
address: 0x5
bitmask: 0x200
# Bit: 10
- platform: modbus_controller
modbus_controller_id: "${devicename}"
name: "${entity_prefix} Function Setting ECO Mode"
id: "${devicename}_function_setting_eco_mode"
register_type: holding
address: 0x5
bitmask: 0x400
# Bit: 11